Connections and units

The top-level modbus_connection package is a pure interface. It defines two ProtocolsModbusConnection and ModbusUnit — and a small exception hierarchy. It also re-exports the shared WordOrder datatype (used by decode / encode and the model framework) for convenient importing — it is not part of the connection surface. The package imports no Modbus library, so you can type against it without committing to a backend.

The two classes have deliberately different roles.

A ModbusConnection is a shared, internally-serialized, already-connected link to a Modbus network. One physical link addresses many units (1–247), and sharing a single connection across many consumers is strictly better than each opening a competing socket.

  • It is transient and owner-held. A backend connect function returns a live, already-connected instance — there is no connect() on the object.
  • Requests are serialized per connection by the backend, not by this wrapper: pymodbus’s transaction manager and tmodbus’s smart transport each hold a lock for the full request/response cycle, so concurrent unit calls on one connection can’t interleave.
  • It does not self-reconnect. On a drop it fires on_connection_lost and stops; recreating it is the owner’s job.
  • Only the owner holds it, and only the owner tears it down with close().
class ModbusConnection(Protocol):
@property
def connected(self) -> bool: ...
def for_unit(self, unit_id: int) -> ModbusUnit: ...
def on_connection_lost(self, callback): ...
async def close(self) -> None: ... # owner only

A ModbusUnit is a stateless handle bound to one unit ID on a shared connection. You obtain it with connection.for_unit(unit_id) and hand it to a consumer (a device library, a Component, …).

  • It holds no buffered state beyond the address.
  • It has no lifecycle methods: a consumer cannot connect or close the link it rides on.
  • Every method raises on any failure (timeout, exception response, link down). It never returns None or swallows errors.
conn = await connect_tcp("192.168.1.50", port=502)
unit = conn.for_unit(1) # a ModbusUnit for station 1
temp = await unit.read_holding_registers(9, 1)

Each backend ships one connect function per wire transport. They are async and return a live ModbusConnection:

import asyncio
from modbus_connection.pymodbus import connect_tcp
from modbus_connection.decode import decode_int16, decode_float32
async def main() -> None:
conn = await connect_tcp("192.168.1.50", port=502)
try:
unit = conn.for_unit(1)
outside_temp = decode_int16(await unit.read_holding_registers(9, 1))
flow_setpoint = decode_float32(await unit.read_holding_registers(40, 2))
pump_on = (await unit.read_coils(56, 1))[0]
print(outside_temp, flow_setpoint, pump_on)
finally:
await conn.close()
asyncio.run(main())

Swapping to tmodbus is a one-line import change — the rest is identical:

from modbus_connection.tmodbus import connect_tcp
Function Transport framer options
connect_tcp(host, *, port=502, framer="socket") Modbus TCP, or RTU-/ASCII-over-TCP (serial-to-Ethernet gateways) socket / rtu / ascii
connect_udp(host, *, port=502, framer="socket") Modbus UDP socket / rtu / ascii
connect_serial(port, *, framer="rtu", baudrate=…, bytesize=…, parity=…, stopbits=…) Modbus serial — RTU or ASCII rtu / ascii
connect_tls(host, *, port=802, verify=True, …) Modbus/TLS (Modbus Security) — (always TLS framing)

framer names the wire framing across every transport; its value set differs by transport (socket/rtu/ascii for TCP/UDP, rtu/ascii for serial; TLS is fixed).

from modbus_connection.pymodbus import connect_udp, connect_serial, connect_tls
udp = await connect_udp("192.168.1.50", port=502)
ascii_serial = await connect_serial("/dev/ttyUSB0", framer="ascii", baudrate=9600)
tls = await connect_tls("device.local") # verifies the server certificate

tmodbus exposes the same functions except connect_udp and connect_tcp(framer="ascii") — it has no UDP or ASCII-over-TCP transport, so those raise NotImplementedError. Use the pymodbus backend for them.

connect_tls verifies the server certificate against the system trust store by default (verify=True) and checks the hostname (check_hostname=True):

  • verify=False — a device with a self-signed certificate.
  • verify="/path/to/ca" — a private CA (file or directory).
  • check_hostname=False — verify the certificate but not the hostname.
  • client_cert / client_key / client_key_password — present a client certificate for mutual TLS.
  • sslctx — pass a ready-made ssl.SSLContext for full control.

Some devices need a pause between frames. Pass message_spacing (seconds) to a connect function and every request — from any unit sharing the link — waits until that gap has elapsed since the previous one finished:

conn = await connect_serial("/dev/ttyUSB0", message_spacing=0.1)

The package applies the gap itself, so it works the same across backends. It is the spacing between requests only — to delay the first request, sleep before issuing it. The default 0 disables it.

message_spacing paces the whole link. When only one slow device on a shared connection needs the pause — and forcing it on every unit would needlessly slow the rest — set the gap on that unit instead:

slow = conn.for_unit(7)
slow.set_message_spacing(0.05) # ≥50 ms between requests to unit 7

It layers on top of any connection-wide message_spacing: a request to the unit waits for whichever gap is longer. The gap belongs to the unit id, not the handle — it applies to every request to that unit, including through other handles handed out for the same id (as when a connection owner lends units to consumers). Pass 0 to clear it.

ModbusUnit exposes the full 19-function-code Modbus surface, not just the common reads and writes:

# Register I/O
await unit.read_holding_registers(address, count) # FC03 -> list[int]
await unit.read_input_registers(address, count) # FC04 -> list[int]
await unit.write_register(address, value) # FC06
await unit.write_registers(address, values) # FC16
# Coils / discrete inputs
await unit.read_coils(address, count) # FC01 -> list[bool]
await unit.read_discrete_inputs(address, count) # FC02 -> list[bool]
await unit.write_coil(address, value) # FC05
await unit.write_coils(address, values) # FC15

Beyond these it also exposes the diagnostic and identification codes — exception status (0x07), diagnostics (0x08), comm-event counter/log (0x0B / 0x0C), report-server-id (0x11), mask-write (0x16), read/write-registers (0x17), FIFO queue (0x18), file records (0x14 / 0x15), and device identification (0x2B/0x0E). A backend that cannot implement a code raises NotImplementedError (tmodbus does, for diagnostics and the comm-event codes).

The raw reads return lists of int (registers) or bool (bits) — no datatype decoding. That lives one layer up.

modbus_connection.decode and .encode turn register words into Python values and back. They are what the raw reads above feed into:

from modbus_connection.decode import decode_int16, decode_float32, decode_string
decode_int16(await unit.read_holding_registers(9, 1)) # signed 16-bit
decode_float32(await unit.read_holding_registers(40, 2)) # IEEE-754 over 2 regs
decode_string(await unit.read_holding_registers(10, 4)) # ASCII over 4 regs

For anything more than a handful of values, prefer the device-modelling framework: it wraps these codecs in typed fields and pools the reads for you.

Every backend maps its errors onto one neutral hierarchy, so except ModbusError catches them all regardless of backend. See Exceptions for the full tree.